AC Surge Joule Rating
150 J
Ratings (VA/W)
1000 VA / 1000 W
Dimensions (mm) Unit, D×W×H
400×430×85
Rated Volatge
230 VAC
Rated Frequency
50 Hz / 60 Hz
Frequency Range
40 to 70 Hz
Power Factor
≥0.99
Input Power Cord
C14
Nominal Voltage
200/208/220/230/240 VAC
Waveform
Sine wave
Inverter Overload Capability
>200% minimum 250 ms, 150 to 200% for 2 seconds; 125 to 150% for 50 seconds; 105 to 125% for 60 seconds
Efficiency in Online Mode
Up to 93%
Output Receptacles
(8) EN60320/C13
Rated Voltage
36 Vdc
Charger Current
Nominal 2.2 A; Maximum 8 A
Type
Valve-regulated, non-spillable, lead acid
Qty x V x Rating
3 x 12 V x 9.0 Ah
End Cell Voltage
1.67 V/cell (discharge voltage per cell will be from 1.67 Vdc to 1.90 Vdc, canbe selected by PARAMSET)
Floating Voltage
Equalize charge 2.35 V/cell; Float charge 2.27 V/cell
Battery Voltage Range
30 Vdc to 42.3 Vdc
Operating Temperature °C
Full power up to 40 ºC (up to 50 ºC with derating)
Storage Temperature °C
20 to 60 ( contain batteries will be from -15 to 40 °C.)
Relative Humidity
0 to 95% non-condensing
Operating Elevation
Up to 3,000 m at 25°C without derating