AC Surge Joule Rating
82J
Ratings (VA/W)
8000 VA / 8000 W
Operating Frequency, Nom
50 or 60 Hz (Factory default is 50 Hz )
Factory Default Voltage
230 VAC
Operating Voltage Range Without Battery Operation
176 to 288 VAC (100 to 176 VAC with power derating)
Maximum Allowable Voltage
288 VAC
Input Frequency Without Battery Operation
40 to 70 Hz
AC-AC Efficiency
94.5%
User-configurable Voltage
200/208/220/230/240 VAC
Frequency
50 Hz or 60 Hz, Nominal
Waveform
Pure Sinewave
Output Power Connection
Output terminal block
Main Mode Overload
>150% minimum 200 ms, 125 – 150% for 60 seconds; 105 – 125% for 5 minutes; ≤ 105% continuous
Charger Current
2.25 A (default), maximum 8 A
Battery Type
Valve-regulated, non-spillable, lead acid
Qty x V x Rating
2 x 8 x 12V x 9.0 AH
Back-up Time at Full Load
3,5
Back-up Time at Half Load
9,5
Upper-limit Selections
+ 10%, + 15%, + 20%; default + 10%
Lower-limit Selections
- 10%, - 15%, - 20%; default - 15%
Disable-bypass Operation
When the input frequency prevents synchronous operation
Amp Rating
63 A
Start Up
Inclusive of Start-up within Metro Manila (additional charge if outside Metro Manila, message us for more info)